What is the application of this thermal overload relay?
The Telemecanique LR2D1308 thermal overload relay is designed for motor protection.
What is the tripping threshold of this relay?
The tripping threshold of the LR2D1308 is 1.14 +/-0.06 In A, conforming to IEC 60947-4-1.
What is the rated operational voltage for this relay?
The rated operational voltage for the LR2D1308 is 690 V AC 50/60 Hz for the power circuit, conforming to IEC 60947-4-1.
What is the network frequency for this thermal overload relay?
The network frequency for the LR2D1308 is 50/60 Hz.
What are the mounting support options for this relay?
The LR2D1308 can be mounted on a plate with EverLink power terminal block or on a rail with EverLink power terminal block.
What is the phase failure sensitivity of this relay?
The LR2D1308 has a phase failure sensitivity with a tripping current of 30% of Ir on one phase, while the others are at Ir, conforming to IEC 60947-4-1.
What is the tightening torque for the control circuit?
The tightening torque for the control circuit of the LR2D1308 is 1.7 N.m on screw clamp terminals.
What is the ambient air temperature range for operation?
The ambient air temperature range for operation of the LR2D1308 is -20 to 60°C, conforming to IEC 60947-4-1.
What is the IP degree of protection for this relay?
The LR2D1308 has an IP degree of protection of IP2x, conforming to VDE 0106.