What is the input voltage range for this inverter drive?
The Siemens 6SL3210-1KE12-3UF2 inverter drive has an input voltage range of 380 to 480 V AC, with a tolerance of +10% and -20%.
What is the output frequency range for vector control and V/f control?
For the Siemens 6SL3210-1KE12-3UF2, the output frequency range for vector control is 0 to 240 Hz, and for V/f control, it is 0 to 550 Hz.
What is the cooling method used for this inverter drive?
The Siemens 6SL3210-1KE12-3UF2 uses air cooling with an integrated fan as its cooling method.
What is the maximum installation altitude for this inverter drive?
The Siemens 6SL3210-1KE12-3UF2 can be installed at a maximum altitude of 1,000 meters (3,280.84 feet).
What is the degree of protection for this inverter drive?
The Siemens 6SL3210-1KE12-3UF2 has a degree of protection of IP20 / UL open type.
What communication protocols does this inverter drive support?
The Siemens 6SL3210-1KE12-3UF2 supports PROFINET and EtherNet/IP communication protocols.
What is the maximum motor cable length for this inverter drive?
For the Siemens 6SL3210-1KE12-3UF2, the maximum motor cable length is 150 meters (492.13 feet) for both shielded and unshielded cables.
What is the overload capability for this inverter drive?
The Siemens 6SL3210-1KE12-3UF2 has a Low Overload (LO) capability of 150% base load current IL for 3 seconds, followed by 110% base load current IL for 57 seconds in a 300-second cycle time. It also has a High Overload (HO) capability of 200% base load current IH for 3 seconds, followed by 150% base load current IH for 57 seconds in a 300-second cycle time.