What is the voltage rating of this overload relay?
The Schneider Overload Relay is rated for 690 V ac.
What is the thermal protection adjustment range of this part?
The thermal protection adjustment range of the Schneider Overload Relay is 63 to 80 A.
What type of mounting support does this part require?
This part can be mounted on a plate with specific accessories, a rail with specific accessories, or under a contactor.
What is the tripping threshold of this overload relay?
The tripping threshold of the Schneider Overload Relay is 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1.
What is the system voltage of this part?
The system voltage of the Schneider Overload Relay is 690 V AC 0...400 Hz.
What is the rated impulse withstand voltage of this part?
The rated impulse withstand voltage of the Schneider Overload Relay is 6 kV.
What is the phase failure sensitivity of this part?
The phase failure sensitivity of the Schneider Overload Relay is tripping current 130% of Ir on two phases, the last one at 0.
What is the temperature compensation range of this part?
The temperature compensation range of the Schneider Overload Relay is -4...140 °F (-20...60 °C).
What is the height, width, and depth of this part?
The Schneider Overload Relay measures 75 x 121 x 123 mm.
What is the weight of this part?
The Schneider Overload Relay weighs 0.51 kg.