What is the thermal protection adjustment range for this thermal overload relay?
The thermal protection adjustment range for the LRD05 is 0.63 to 1 A.
What is the overload tripping class for this part?
The LRD05 has an overload tripping class of 10A, conforming to IEC 60947-4-1.
What is the rated insulation voltage for this part?
The rated insulation voltage for the LRD05 is 690 V for the power circuit, conforming to IEC 60947-4-1, and 600 V for the power circuit, conforming to UL and CSA standards.
What is the phase failure sensitivity for this thermal overload relay?
The LRD05 has a phase failure sensitivity with a tripping current of 130% of Ir on two phases, and the last one at 0.
What is the temperature compensation range for this part?
The temperature compensation range for the LRD05 is -30 to 60 °C.
What is the IP degree of protection for this thermal overload relay?
The LRD05 has an IP20 degree of protection, conforming to IEC 60529.
What is the product compatibility for this thermal overload relay?
The LRD05 is compatible with LC1D09 to LC1D38 contactors.
What is the network frequency range for this part?
The network frequency range for the LRD05 is 0 to 400 Hz.
What are the connection types and tightening torque for this thermal overload relay?
The LRD05 has screw clamp terminals for both power and control circuits. The tightening torque for both circuits is 1.7 N.m.