Part Number |
33559 |
Manufacturer |
Schneider |
Product Name |
Circuit breaker, ComPact NS1000H |
Range |
ComPact |
Product Type |
Circuit breaker |
Device Application |
Distribution |
Number of Poles |
3 poles |
Rated Current |
1000 A at 50 °C |
Rated Operational Voltage |
690 V AC 50/60 Hz |
Network Type |
AC |
Network Frequency |
50/60 Hz |
Suitability for Isolation |
Yes, conforming to EN/IEC 60947-2 |
Utilisation Category |
Category B |
Rated Ultimate Short-Circuit Breaking Capacity |
70 kA at 415 V AC 50/60 Hz, 65 kA at 440 V AC 50/60 Hz, 42 kA at 660/690 V AC 50/60 Hz, 85 kA at 220/240 V AC 50/60 Hz, 50 kA at 500/525 V AC 50/60 Hz |
Performance Level |
H 70 kA 415 V AC |
Trip Unit Name |
MicroLogic 5.0 |
Trip Unit Technology |
Electronic |
Trip Unit Protection Functions |
LSI |
Control Type |
Rotary handle, Toggle |
Circuit Breaker Mounting Mode |
Fixed |
Rated Insulation Voltage |
800 V AC 50/60 Hz conforming to IEC 60947-2 |
Rated Impulse Withstand Voltage |
8 kV conforming to IEC 60947-2 |
Rated Service Short-Circuit Breaking Capacity |
50 kA at 380/415 V AC 50/60 Hz, 30 kA at 660/690 V AC 50/60 Hz, 40 kA at 500/525 V AC 50/60 Hz, 50 kA at 440 V AC 50/60 Hz, 50 kA at 220/240 V AC 50/60 Hz |
Rated Short-Time Withstand Current |
19.2 kA 1 s conforming to IEC 60947-2 |
Mechanical Durability |
10,000 cycles |
Electrical Durability |
2,000 cycles at 690 V In, 4,000 cycles at 690 V In/2, 5,000 cycles at 440 V In, 6,000 cycles at 440 V In/2 |
Power Losses |
22 W |
Mounting Support |
Backplate |
Connection Type |
Front |
Connection Pitch |
70 mm |
Protection Type |
L: for overload protection (long time), S: for short time short-circuit protection, I: for instantaneous short-circuit protection |
Trip Unit Rating |
1000 A at 50 °C |
Long-Time Pick-Up Adjustment Type |
Adjustable 9 settings |
Long-Time Protection Pick-Up Adjustment Range |
0.4...1 x In |
Long-Time Protection Delay Adjustment Type |
Adjustable 9 settings |
Long-Time Protection Delay Adjustment Range |
12.5…600 s at 1.5 x Ir, 0.5…24 s at 6 x Ir, 0.7…16.6 s at 7.2 x Ir |
Thermal Memory |
20 mn |
Short-Time Protection Pick-Up Adjustment Type |
Adjustable 9 settings |
Short-Time Protection Pick-Up Adjustment Range |
1.5...10 x Ir |
Short-Time Protection Delay Adjustment Type |
Adjustable |
Short-Time Protection Delay Adjustment Range |
0.1…0.4 s I²t=on, 0…0.4 s I²t=off |
Instantaneous Protection Pick-Up Adjustment Type |
Adjustable |
Instantaneous Protection Pick-Up Adjustment Range |
Off, 2...15 x In |
Earth-Leakage Protection |
Without |
Zone Selective Interlocking (ZSI) |
Without |
Auxiliary Contact Composition |
1 NO/NC |
Local Signalling |
4 LEDs (red) for fault indication, 1 LED (yellow) for overload |
Width |
210 mm |
Height |
327 mm |
Depth |
147 mm |
Net Weight |
14 kg |
Standards |
EN/IEC 60947-2 |
Product Certifications |
ASTA, ASEFA |
Pollution Degree |
3 conforming to IEC 60947 |
IP Degree of Protection |
IP40 conforming to IEC 60529 |
IK Degree of Protection |
IK07 conforming to EN 50102 |
Ambient Air Temperature for Operation |
-25…70 °C |
Ambient Air Temperature for Storage |
-50…85 °C |
Relative Humidity |
0…95 % |
Operating Altitude |
0...2000 m without derating, 2000 m...5000 m with derating |
Sustainable Offer Status |
Green Premium product |
REACh Regulation |
REACh Declaration |
EU RoHS Directive |
Compliant with Exemptions |
Mercury Free |
Yes |
China RoHS Regulation |
China RoHS Declaration |
RoHS Exemption Information |
Yes |
Environmental Disclosure |
Product Environmental Profile |
Circularity Profile |
End Of Life Information |
WEEE |
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins |