What is the input range for this analogue input module?
The Omron DRT2-AD04 has an input range for signals of 0 to 5 V, 1 to 5 V, 0 to 10 V, -10 to 10 V for voltage input and 0 to 20 mA, 4 to 20 mA for current input.
How is the input range setting method for this module?
The input range setting method for the DRT2-AD04 can be done using a DIP switch with common settings for inputs 0 and 1 and common settings for inputs 2 and 3. Alternatively, independent settings for inputs 0 to 3 can be done using a Configurator.
What is the resolution of this analogue input module?
The resolution of the DRT2-AD04 is 1/6000 (full scale).
What is the conversion time for this module?
The analogue conversion cycle when using 4 points is 4 ms max. It is 2 ms per point.
What is the isolation method used in this module?
The DRT2-AD04 uses photocoupler isolation between input and communications lines.
What is the current consumption of this module?
The current consumption of the DRT2-AD04 is 90 mA max. at 24VDC.
What is the ambient operating temperature for this module?
The ambient operating temperature for the DRT2-AD04 is -10°C to 55°C.
What is the weight of this module?
The weight of the DRT2-AD04 is 170 g max.
What are the dimensions of this module?
The dimensions of the DRT2-AD04 are 49.7 x 115 x 53.1 mm.
What is the functionality of this module?
The DRT2-AD04 has several functions including scaling, peak/valley hold function, integration function, differentiation function, and settings confirmation via DeviceNet.