What is the voltage range for the digital input terminal?
The nominal voltage for the KL1408 digital input terminal is 24 V DC, with a range of -15% to +20%.
What are the signal voltage levels for the '0' and '1' states?
For the KL1408, the '0' signal voltage is -3 to +5 V (EN 61131-2, type 1/3), and the '1' signal voltage is 11 to 30 V (EN 61131-2, type 3).
What is the input filter time for this digital input terminal?
The KL1408 digital input terminal has an input filter time of 3.0 ms.
What is the operating temperature range for this part?
The KL1408 digital input terminal has an operating temperature range of 0°C to +55°C.
What is the storage temperature range for this part?
The KL1408 digital input terminal has a storage temperature range of -25°C to +85°C.
What is the protection class and installation position for this part?
The KL1408 digital input terminal has a protection class of IP20 and a variable installation position.
How many input channels does this digital input terminal have?
The KL1408 digital input terminal has 8 input channels.
What is the electrical isolation between the K-bus and field potential?
The KL1408 digital input terminal has an electrical isolation of 500 V between the K-bus and field potential.
What is the current consumption of the K-bus?
The KL1408 digital input terminal has a typical current consumption of 5 mA for the K-bus.