What is the main function of this communication interface module?
The X20CS1030 is a communication interface module designed for use with B&R's X20 system. It serves as a bus receiver for CAN I/O, providing power supply for the X2X Link and internal I/O power supply.
What are the operating conditions for this module?
The X20CS1030 can be mounted horizontally or vertically and operates at an elevation of 0 to 2000 meters above sea level. The ambient temperature range for horizontal mounting is -25 to 60°C, while for vertical mounting it is -25 to 50°C. The module has a degree of protection of IP20.
How do I set the node number for this module?
The X20CS1030 module can be set to node number 1 or 2. By default, it is set to node number 1. To set it to node number 2, connect terminal connections 14 and 24 using a jumper.
Is a terminating resistor required for the CAN network?
Yes, a terminating resistor is required for the CAN network. Both ends of the bus must be wired with a terminating resistor, which must be wired externally.
What is the maximum distance and transfer rate for the CAN I/O fieldbus?
The maximum distance for the CAN I/O fieldbus is 1000 meters, and the maximum transfer rate is 1 Mbit/s. The module also features automatic transfer rate detection.
What is the power consumption of the X2X Link power supply?
The power consumption of the X2X Link power supply for the X20CS1030 module is 0.6 W.
What type of fuse is required for the module?
A maximum 10 A slow-blow fuse is required for wiring the X20CS1030 module.
How many logical I/O module slots can be connected to this bus receiver?
Up to 43 I/O modules can be connected to the X20CS1030 bus receiver, with up to 16 of these being analog modules. This value refers to logical I/O module slots, not physical ones.