What is the input current of this part?
The input current from the supply voltage 1L+ is a maximum of 75 mA. From the load voltage 2L+ and 3L+ (without load), it is a maximum of 100 mA.
What is the power loss of this part?
The typical power loss for this part is 12 W.
How many digital outputs does this part have?
This part has 8 digital outputs.
What is the switching capacity of the outputs?
The switching capacity of the outputs on lamp load is a maximum of 5 W.
What is the output current for signal '1'?
The rated value for signal '1' is 2 A. The permissible range for 0 to 40 °C is a minimum of 7 mA and a maximum of 2 A for horizontal installation, 1 A for vertical installation. The permissible range for 40 to 60 °C is a minimum of 7 mA and a maximum of 1 A for horizontal installation.
What is the switching frequency of this part?
The maximum switching frequency with resistive load is 30 Hz, with inductive load is 2 Hz, and on lamp load is 10 Hz.
What is the total current of the outputs per group?
For horizontal installation, the total current of the outputs per group is up to 7.5 A at 40 °C and up to 5 A at 60 °C. For vertical installation, it is up to 5 A at 40 °C.
What is the maximum cable length for this part?
The maximum cable length for this part is 200 m, both for shielded and unshielded cables.
Does this part have diagnostic alarms?
Yes, this part has diagnostic alarms that are parameterizable.
Does this part have potential separation between the channels and the power supply of the electronics?
Yes, this part has potential separation between the channels and the power supply of the electronics.