What is the current carrying capacity of this base unit?
The base unit has a maximum current carrying capacity of 10 A for P1 and P2 bus, 10 A for the AUX bus, and 2 A for the process terminals.
What are the dimensions of this base unit?
The dimensions of this base unit are 141 mm in height, 15 mm in width, and 35 mm in depth.
What is the weight of this base unit?
The approximate weight of this base unit is 50 g.
What is the supply voltage for this base unit?
The rated supply voltage for this base unit is 24 V DC.
What type of terminals does this base unit have?
This base unit has push-in terminals.
What is the maximum conductor cross-section this base unit can accommodate?
The base unit can accommodate a conductor cross-section of minimum 0.14 mm² and maximum 2.5 mm².
What is the ambient temperature range for operation of this base unit?
The base unit can operate in an ambient temperature range of -30 °C to 60 °C for horizontal installation and -30 °C to 50 °C for vertical installation.
What is the maximum installation altitude for this base unit?
The maximum installation altitude for this base unit is 5000 m above sea level.
Does this base unit form a new potential group?
No, this base unit does not form a new potential group. It continues the potential group from the left.
What is the hardware configuration of this base unit?
This base unit has a type A0 hardware configuration.