What type of device is the Sick 1085345?
The Sick 1085345 is a safety relay, specifically the RLY3-EMSS100 model, designed for industrial safety applications.
What are the main features of this safety relay?
The Sick 1085345 safety relay features dual-channel emergency switching off, manual reset, and external device monitoring. It supports safety integrity level SIL3 and performance level PL e.
What is the power supply requirement for this safety relay?
The Sick 1085345 requires a supply voltage of 24 V DC, with an operating range between 16.8 V and 30 V DC.
How many safety inputs does the Sick 1085345 have?
The Sick 1085345 safety relay is equipped with two safety inputs.
What is the response time of the Sick 1085345?
The response time for the enabling current paths of the Sick 1085345 is 10 milliseconds.
What is the mechanical life expectancy of this safety relay?
The Sick 1085345 has a mechanical life expectancy of 10 million switching cycles.
What type of outputs does the Sick 1085345 provide?
The Sick 1085345 provides two enabling current paths with normally open contacts and two application diagnostic outputs.
What are the dimensions of the Sick 1085345?
The dimensions of the Sick 1085345 safety relay are 18 mm x 124.6 mm x 85.5 mm.
What is the operating temperature range for the Sick 1085345?
The operating temperature range for the Sick 1085345 is from -25 °C to +55 °C.
Is the Sick 1085345 suitable for use in environments with high humidity?
Yes, the Sick 1085345 can operate in environments with humidity levels up to 95%, non-condensing.