What is the function of this circuit breaker?
The GV2P14 is a motor circuit breaker designed to protect an electrical circuit from damage caused by excess current from an overload or short circuit. It interrupts the electrical flow upon detecting a fault condition.
What are the technical specifications of this circuit breaker?
This circuit breaker is a 3 Pole device with a rated current of 10 A and operational voltage of 690 V ac. It has a thermal protection adjustment range of 6 to 10 A and a magnetic tripping current of 138 A. The device is suitable for isolation and has a phase failure sensitivity.
What are the physical dimensions of this circuit breaker?
The GV2P14 circuit breaker measures 45 x 97 x 89 mm.
What is the breaking capacity of this circuit breaker?
The GV2P14 has a breaking capacity of 100 kA Icu at 230/240 V AC 50/60 Hz, 400/415 V AC 50/60 Hz, and 440 V AC 50/60 Hz. It also has a breaking capacity of 50 kA Icu at 500 V AC 50/60 Hz and 6 kA Icu at 690 V AC 50/60 Hz.
What is the operating temperature range of this circuit breaker?
The GV2P14 can operate in ambient air temperatures ranging from -20 to 60 degrees Celsius.
What certifications does this circuit breaker have?
The GV2P14 circuit breaker is certified by CCC, UL, CSA, EAC, ATEX, LROS, BV, RINA, DNV-GL, and UKCA.
What is the power dissipation per pole of this circuit breaker?
The power dissipation per pole of the GV2P14 circuit breaker is 2.5 W.
What is the tightening torque of this circuit breaker?
The tightening torque of the GV2P14 circuit breaker is 1.7 N.m.
What is the mechanical and electrical durability of this circuit breaker?
The GV2P14 circuit breaker has a mechanical durability of 100,000 cycles and an electrical durability of 100,000 cycles for AC-3 at 415 V In.