What is the operating voltage of this electronic circuit protection?
The operating voltage of the Murr Elektronik electronic circuit protection is 24 V DC (18...30 V DC).
What are the current adjustment options for this part?
The current can be adjusted to 1 A, 2 A, 4 A, or 6 A using a countersink rotary switch.
What is the inrush capacity of this part?
The inrush capacity of the Murr Elektronik electronic circuit protection is a maximum of 20 mF per channel.
What is the control input voltage for this part?
The control input voltage for the Murr Elektronik electronic circuit protection is 10...30 V DC.
What is the impulse length for this part?
The impulse length for the Murr Elektronik electronic circuit protection is a minimum of 20 ms.
What is the group alarm output for this part?
The group alarm output for the Murr Elektronik electronic circuit protection is potential free 30 V AC/DC, 100 mA.
What is the mounting method for this part?
The Murr Elektronik electronic circuit protection is DIN-rail mountable TH 35 (EN 60715).
What is the temperature range for this part?
The temperature range for the Murr Elektronik electronic circuit protection is 0...+55 °C (storage temperature -40...+80 °C).
What is the connection type for this part?
The Murr Elektronik electronic circuit protection uses spring clamp terminals for connection.
What are the dimensions of this part?
The dimensions of the Murr Elektronik electronic circuit protection are 90×36×80 mm.