What is the actuator type used in this miniature circuit breaker?
The Schneider A9F74103 miniature circuit breaker uses a toggle actuator.
What are the dimensions of this circuit breaker?
The dimensions of the circuit breaker are 18 mm in width, 78.5 mm in depth, and 85 mm in height.
Can this circuit breaker be used with both AC and DC power systems?
Yes, the Schneider A9F74103 is suitable for use with both AC and DC power systems.
What is the rated current of this circuit breaker?
The rated current of the circuit breaker is 3 A.
What are the breaking capacities of this device?
This device has a breaking capacity of 6000 A at 230 V AC under IEC/EN 60898-1 and up to 50 kA under IEC/EN 60947-2 for various voltage ranges.
What type of connections can be used with this circuit breaker?
The circuit breaker supports connections using single terminals for both rigid and flexible wires, accommodating wire sizes from 1 to 25 mm² for rigid and 1 to 16 mm² for flexible wires.
What is the IP degree of protection for this circuit breaker?
The IP degree of protection for the Schneider A9F74103 is IP20.
Does this circuit breaker have a trip indicator?
Yes, it includes a trip indicator for local signalling.
What are the environmental operating conditions for this circuit breaker?
The circuit breaker can operate in ambient air temperatures ranging from -35°C to 70°C and can be stored in temperatures from -40°C to 85°C.
How is this circuit breaker mounted?
It is designed for fixed mounting on a DIN rail.