What is the primary function of this bus coupler?
The primary function of the Beckhoff EK9000 bus coupler is to connect Ethernet networks to EtherCAT Terminals and EtherCAT Box modules, converting Ethernet telegrams to E-bus signal representation.
Which protocols does this bus coupler support?
The Beckhoff EK9000 bus coupler supports Modbus TCP and Modbus UDP protocols.
What are the power supply requirements for this bus coupler?
The Beckhoff EK9000 requires a power supply of 24 V DC with a tolerance of -15% to +20%.
How many RJ45 interfaces does this bus coupler have?
The Beckhoff EK9000 bus coupler is equipped with two RJ45 interfaces that are switched.
What is the typical input current for this bus coupler?
The typical input current for the Beckhoff EK9000 is 120 mA plus the total E-bus current divided by four.
What is the maximum current consumption on the E-bus?
The maximum current consumption on the E-bus for the Beckhoff EK9000 is up to 2 A.
What are the dimensions of this bus coupler?
The dimensions of the Beckhoff EK9000 bus coupler are 64 mm in width, 100 mm in height, and 73 mm in depth.
What is the operating temperature range for this bus coupler?
The Beckhoff EK9000 bus coupler operates within a temperature range of 0°C to 55°C.
Is configuration required for this bus coupler?
No configuration is required for the Beckhoff EK9000 bus coupler.
What level of electrical isolation does this bus coupler provide?
The Beckhoff EK9000 provides electrical isolation of 500 V between power contact, supply voltage, and Ethernet.